Kitchen Extract

Thor Duct®
Kitchen Extract Ductwork




Kitchen extract poses a specific fire risk due to the presence of combustible contaminants, namely grease. Kitchen extract ducts that pass through multiple fire compartments on their way to the outside, are at risk of being exposed to a fire in those compartments. This is outside the kitchen compartment itself. The concern is that a fire will reach the kitchen ductwork that passes through the compartment and cause the grease inside the duct to ignite.

The protection offered by compartmentation is no longer certain as the fire may cascade along the route of the kitchen extract ductwork. The grease in question, due to the process of oxidation, has a low flash point of 180°C. The fire can spread back to the kitchen and all compartments enroute. Thor Duct® is a solution, based on the latest EN1366-1 requirements, tested with Insulation to delay a temperature rise of 180°C inside the ductwork.

Compliance with EN1366-1

Includes testing ducts under 'Type A' fire, with measuring devices (thermocouples) surface mounted inside the ductwork, inside the furnace, tested to the fire curve EN1363-1. The insulated ductwork is examined to measure how many minutes it can maintain the duct temperature below 180°C on any one thermocouple, or below 140°C as a mean average of all thermocouples.

Insulation

Thor Duct® Kitchen Extract is insulated using a calcium magnesium silicate blanket which maintains the duct temperature below 180°C and prevents grease igniting and causing fire to spread throughout the building. This insulation was tested as a combined system (ductwork + Insulation) and evidenced by way of test reports and classification to the standard EN13501-3.

Thor Duct® Cleaning Doors EN 1366-1





Thor Duct® Cleaning Doors have been tested to EN 1366-1 and are suitable for kitchen extracts. Cleaning doors are required every 2 linear meters. We strongly recommend a routine cleaning regime by specialist contractors.



KEY FEATURES


Compliance with EN Code

Thor Duct® Kitchen Extract is comprehensively tested to satisfy all code requirements.

  • EN13501-3 Classification
  • EN1366-1 with Thor Duct® Cleaning Doors

Fully Tested

Thor Duct® Kitchen Extract is tested in a flexible wall with:

  • Insulated and uninsulated
  • Horizontal and vertical orientations
  • Fire types A and B
  • Square & round orientations

Installation

All Thor Duct® Kitchen Extract systems are installed by third party certified installers and are suitable for installation in:

  • Stud partition
  • Block wall
  • Concrete floors
  • Detailed penetration requirements provided in our installation guides

Product Sizes

  • Square standard maximum size available up to 2500x1250mm
  • Round up to 1000 Ø
  • Performance of Ø ducts differs from square ducts
  • Thor Duct® is manufactured from Galvanised Steel, and uses flanges and stiffeners, without paints or coatings.
  • Thor Duct® is insulated using a calcium magnesium silicate blanket.

Both the product and the insulation have been tested as a system in accordance with test standards which includes access doors, silencers and bracketry.

All tests were conducted in EOTA approved laboratories, and each licensed manufacturing location has a factory production control (FPC) in place to ensure exacting standards of manufacture.

MANUFACTURING
STANDARDS

INSTALLATION STANDARDS





You can be 100% sure that your installation has been properly managed and is fit for purpose when called upon in the event of a fire.

  • Penetration seal detail is provided for floors and walls. Thor Duct® is suitable for installation in flexible walls (Plasterboard) and aerated concrete floors, having been tested in both.
  • Our installers in Ireland and the UK comply with local guidance and are all members of third party certification schemes.
  • In mainland Europe, installers comply with certification schemes where available